CHARGOMATIC C100-1,5

  • Battery charger
  • Linearly synchronized
  • Chassis
12 V 1,5 A
12 V 1,5 A


Description



Mechanical design
The devices of the C100-1,5 series are designed as a charger for continuous operation. When used in stand-by parallel mode the user load should not rise above 1A.

All devices are equipped with network terminals, separate terminals for output and battery as well as fuses for output and battery as standard. The standard version is configured for 230 V, 50/60 Hz. Different mains voltages are also available in a special version.

Certification and CE marking
The devices meet the basic requirements of the law relating for electromagnetic compatibility (89/336/EEC EEC Treaty).

Options
  • When used as a charger, a LED on the board or externally can be connected as a charge indicator. The threshold is adjustable from 200 to 400 mA.
  • Temperature compensation

Data

Technical data

Device C112–1,5 C124–1,5
Rated voltage 12 V 24 V
Nominal output current 1,5 A 1,5 A
Tuning voltage 13,8 V 27,6 V
Current limit from 1,5 - 1,7 A
Short-circuit current 0,4 A 0,01 A
IU characteristic IU
Back current at mains failure about 15 mA 22 mA
Input current at 230 V 0,2 A 0,32 A
Line voltage AC, 50/60 Hz 115 V/230 V
± 10%
115 V/230 V
± 10%
Ambient temperature range -10º C/+40º C -10º C/+35º C
Output voltage ripple at 0.75 A < 0,1% pp
Accuracy of the output voltage between 216-244 V for mains voltage at 0.75 A < ± 0,05%
Reverse polarity Protection
Battery output load regulation 1% 0,5%
Load regulation consum at 0.75 A 0,2% 0,1%
Cross section max. 2,5 mm²
Chassis design Aluminum brackets
Radio interference network side EN 55014
Protection class I/VDE 0805
Cooling Convection cooling, aluminum profiles
Humidity, bearing 95% non-condensing
Humidity, operating 80% non-condensing
Dimensions (L x B x H) 160 x 100 x 75 mm
Dial Engineering AG · Langfeldstrasse 96 · CH-8500 Frauenfeld · Tel. +41 52 723 0575 · Fax +41 52 723 0576 · info@dial-eng.ch

A TreeCone Group Company · www.TreeCone.ch
© 2018